Product Name: YA-CP100

Model No.
Description Parameters
  •  Features 

    External (key-switch operated):

    • Reset/resound/test zone lamps evacuate

    • Silence alarm sounders

    • Silence fault sounders

    Internal:

    • One man detector test

    • Zone isolate

    • Revert to short-circuit: fire (no resistors in call points)

    External indicators:

    • Sounder fault

    • Battery/power supply fault

    • Mains on

    • Zone fire

    • Zone fault

    Internal indicators:

    • Open circuit zone fault

    • Short circuit zone fault

    • Zone isolated

    • Engineer test selected

    Outputs:

    • Two sounder circuits (alarm relay contacts can be obtained by connecting a relay to a sounder circuit)

    Ancillary connections for expansion modules will allow the following:

    • Repeater panels

    • Multiple sounder outputs

    • Connection to landlord panel

     

     Specifications 


     2 (0.8A SUPPLY)

     4 / 6 (1.5A SUPPLY)

    8/10/12/14/16/18

    (4.0A SUPPLY)

    POWER SPECIFICATION

    MAINS SUPPLY VOLTAGE

    230V±10%Va.c.50/60Hz

    230V±10%Va.c.50/60Hz

    230V±10%Va.c.50/60Hz

    INTERNAL POWER SUPPLY

    27 Vd.c.

    27 Vd.c.

    27 Vd.c.

    TOTAL OUTPUT CURRENT LIMITED TO

    800mA@240VAC

    1500mA@240VAC

    4000mA@240VAC

    AUXILIARY POWER OUTPUT

    27 Vd.c.

    27 Vd.c.

    27 Vd.c.

    MAINS SUPPLY MONITORED FOR FAILURE

    YES

    YES

    YES

    BATTERY CHARGER MONITORED FOR FAILURE

    YES

    YES

    YES

    BATTERIES MONITORED FOR DISCONNECTION AND FAILURE

    YES

    YES

    YES

    DETECTOR CIRCUIT SPECIFICATION

    NUMBER OF CIRCUITS

    2

    4 or 6

    8, 10, 12, 14,16,or 18

    LINE FAULT MONITORED FOR OPEN CIRCUIT

    YES

    YES

    YES

    LINE FAULT MONITORED FOR SHORT CIRCUIT

    YES (Can be disabled)

    YES (Can be disabled)

    YES (Can be disabled)

    LINE FAULT MONITORED FOR DETECTOR REMOVAL

    Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor

    END OF LINE RESISTOR (SUPPLIED) VALUE

    6800,5% tolerance,0.25W

    6800,5% tolerance,0.25W

    6800,5% tolerance,0.25W

    DETECTOR CONTINUITY DIODES

    Silicon 1N4001 or Schottky type(required if End of Line Monitor Unit fitted to give Detector Removal Fault)

    CALL POINT RESISTOR VALUE (NOT SUPPLIED)

    470 to 680, 0.5W

    470 to 680, 0.5W

    470 to 680, 0.5W

    MAXIMUM NUMBER OF SMOKE DETECTORS PER ZONE

    20(maximum detector current = 2mA)  

    20(maximum detector current = 2mA)  

    20(maximum detector current = 2mA)  

    MAXIMUM NUMBER OF MANUAL  CALL POINTS PER ZONE

    No limit

    No limit

    No limit

    SOUNDER CIRCUIT SPECIFICATION

    NUMBER OF CIRCUITS

    2

    2

    2

    END OF LINE RESISTOR VALUE

    6800, 5%tolerance,0.25W

    6800, 5%tolerance,0.25W

    6800, 5%tolerance,0.25W

    LINE FAULT MONITORED  FOR OPEN CIRCUIT

    YES

    YES

    YES

    LINE FAULT MONITORED FOR SHORT CIRCUIT

    YES

    YES

    YES

    OUTPUTS FUSED AT

    1 Amp

    1 Amp

    1.6 Amp

    MAXIMUM TOTAL OUTPUT CURRENT ALL OUTPUTS

    800mA

    1500mA

    4000mA

    MAXIMUM NO OF BELLS @ 25 mA EACH BELL

    32

    56

    120

    MAXIMUM NO OF ELECTRONIC SOUNDERS @ 20 mA

    40

    70

    150

    AUXILIARY RELAY CONTACTS  (DO NOT CONNECT MAINS VOLTAGES)

    1A 30 Vd.c. max  Voltage Free

    1A 31 Vd.c. max  Voltage Free

    1A 32 Vd.c. max  Voltage Free

    FUSES-ALL FUSES COMPLIANT TO IEC (EN60127 PT2)

    MAINS TERMINAL BLOCK

    200mA T 20 mm

    400mA T 20mm

    630mA T 20mm

    SOUNDER OUTPUTS

    1A F 20mm

    1A F 20mm

    1.6A F 20mm

    AUXILIARY OUTPUT

    1A F 20mm

    1A F 20mm

    1A F 20mm

    BATTERY FUSE

    1.6A F 20mm

    1.6A F 20mm

    3A F 20mm

    DOOR RETAINING MAGNETS

    DO NOT USE PANEL POWER SUPPLY AS YOU WILL DRASTICALLY REDUCE BATTERY STAND-BY TIME

    CONNECTION BLOCK

    LARGEST ACCEPTABLE CONDUCTOR SIZE

    2.5mm2

    2.5mm2

    2.5mm2

    SMALLEST ACCEPTABLE CONDUCTOR SIZE

    0.75mm2

    0.75mm2

    0.75mm2

    DIMENSIONS

    ENCLOSURE(WIDTH x HEIGHT x DEPTH)

    415 x 265 x 100mm

    415 x 265 x 100mm

    415 x 265 x 100mm

    WEIGHT(WITHOUT BATTERIES)

    5100g

    5200g

    5500g



Shenzhen Usafe Intelligent Technology Co., Ltd
Address:5/F, Bldg. 3, Baolaite Industrial Park, No.24 Xinbu Road, Tongle, Longgang District,Shenzhen, China

Tel: +86-755-28286305    Alibaba : szusafe.en.alibaba.com
Fax: +86-755-28289702    Globalsources : szusafe.manufacturer.globalsources.com
E-mail: info@szusafe.com    Website : www.szusafe.com www.cnusafe.com

Shenzhen Usafe Intelligent Technology Co., Ltd 粤ICP备17122624号-1