Features
• 1-10 zones fire alarm control panel
• Up to 35 conventional smoke and/or heat detectors per zone
• AUX DC24V outputs
• Test and silence function
• 2 sounder circuits
• High power relay output
• Power Supply Output: DC24V/3.5A (>7 ZONE)
DC24V/2.5A (<7 ZONE)
• Fault Monitoring: Supply Fault, Battery Fault, Sounder Fault, Zone Fault (open or short circuit),
Detector Removal Fault
• Indication of EARTH fault
• Fault relay output, NC/NO optional
• Alarm relay output, NC/NO optional
• Zone alarm relay output of 5 adjacent zone, NC/NO optional
• 10 zone enable/disable settings
• Enable/disable settings: GND, power supply, sounder, zone open circuit, zone short circuit, relay output
• Terminal blocks wiring connection
Specifications
• Power Supply Voltage: AC220V±15%
• Operating Humidity: 10%-95%RH (non-condensing)
• Operating Temperature: -10℃~+55℃
• Power Supply Output: DC 24V 3.5A (>7 zone), DC 24V 2.5A (<7 zone)
• Zone Output Voltage: DC24V
• Auxiliary Supply Output: DC24V
• Number of Detection Zone: 1-10 ZONE
• Backup Battery: DC12V/7A*2PCS
• Mains Fuse: AC250V/1.5A
• EOL Resistor: 4.7-10KΩ
• Alarm Resistor: 470-1KΩ
• Alarm Relay: 250VAC / 8A
• Fault Relay: 250VAC / 10A
• Zone Alarm Relay: 250VAC/ 10A
• Dimensions: 395*325*95mm
Shenzhen Usafe Intelligent Technology Co., Ltd Tel: +86-755-28286305 Alibaba : szusafe.en.alibaba.com |
Shenzhen Usafe Intelligent Technology Co., Ltd 粤ICP备17122624号-1 |